فواصل الهواء والسائل · معدات التحكم بالبخار
فاصل هواء ضغط عالٍ
This air eliminator removes air and gases from heating, cooling and other liquid circuits. A float and lever open the vent when air arrives and close it when water lifts the float. Higher pressure class than the standard liquid-circuit unit.
مشاركة
The air drainer is used to remove air and gases from the system, especially in heating and cooling lines and other fluid liquid systems. Aeration is performed by a float and lever. When air or other gases come in to the device, the valve opens and starts evacuation. When water arrives, it lifts the float and closes the orifice. Sealing against water is ensured. This cycle continues automatically
- Installation: – The air drainer should be mounted at the highest point system.
- Do not use elbows on entry lines. Use one valve in front of the entrance, so you can isolate the air drainer from the system for repair and cleaning.
- It can be installed horizontally but it should not be preferred except in very obligatory situations
- WORKING CONDITIONS Max. Working Pressure: PN 25
- Max. Working Temp.: 198°C
- Dia (inch): 3/4"x1/2"
| المعامل | القيمة |
|---|---|
| Type | فاصل هواء ضغط عالٍ |
| Series | فواصل الهواء والسائل |
| Service | Steam, condensate and process systems |
| Connections | Threaded, flanged or to project specification |
| Selection | Share fluid, pressure, temperature and duty for a matching selection |
أرسل متطلبات المشروع. يرد فريقنا باختيار مناسب.